Essential details
Shipping:Express
Product Introduction
As primary distribution equipment for gas-insulated single and double busbar systems, the XGNZ9 is mainly applied in substations, distribution stations, and various infrastructure projects including buildings, government offices, steel plants, rail transit facilities, and water treatment projects. It is also applicable to other industries that meet the relevant electrical parameter and design scheme requirements.
Safety
All functional compartments are fully independent. High-voltage components are completely sealed and free from external interference. The insulation performance remains unaffected by the on-site altitude. Equipped with a comprehensive interlock and locking design, as well as reliable internal arc resistance performance, the equipment fully ensures operator safety.
All functional compartments are fully independent. High-voltage components are completely sealed and free from external interference. The insulation performance remains unaffected by the on-site altitude. Equipped with a comprehensive interlock and locking design, as well as reliable internal arc resistance performance, the equipment fully ensures operator safety.
Miniaturization
Featuring a compact structure, the equipment achieves higher space utilization and saves urban land resources. Compared with traditional switchgears, it reduces floor space by up to 70%.
Featuring a compact structure, the equipment achieves higher space utilization and saves urban land resources. Compared with traditional switchgears, it reduces floor space by up to 70%.
Economy
The equipment supports convenient operation and boasts a long service life with strong environmental adaptability and low maintenance requirements, which greatly reduces overall operating costs. Compared with conventional switchgears, it delivers a longer service cycle to avoid repeated replacement investment. Meanwhile, its compact size cuts capital construction and space costs, significantly lowering the total project investment.
The equipment supports convenient operation and boasts a long service life with strong environmental adaptability and low maintenance requirements, which greatly reduces overall operating costs. Compared with conventional switchgears, it delivers a longer service cycle to avoid repeated replacement investment. Meanwhile, its compact size cuts capital construction and space costs, significantly lowering the total project investment.
Electrical Parameters
| S/N | Parameter Name | Unit | Specification |
1 | Rated Voltage | kV | 40.5 |
| 2 | Rated Frequency | Hz | 50 |
| 3 | 1min Power Frequency Withstand Voltage (RMS) *(Phase to Phase, Ground / Fracture)* | kV | 95/118 |
| 4 | Lightning Impulse Withstand Voltage (RMS) *(Phase to Phase, Ground / Fracture)* | kV | 185/215 |
| 5 | Rated Current | A | 630, 1250, 2000, 2500, 3150, 4000 |
| 6 | Rated Short Circuit Breaking Current | kA | 25, 31.5, 40 |
| 7 | Rated Short Time Withstand Current / Duration | kA/s | 25/4, 31.5/4, 40/4 |
| 8 | Rated Peak Withstand Current | kA | 63, 80, 100 |
| 9 | Rated Short Circuit Making Current (Peak) | kA | 63, 80, 100 |
| 10 | Protection Degree of Gas-filled Enclosure | IP | 67 |
| 11 | Protection Degree of Cabinet | IP | 4X |
| 12 | Rated Pressure of SF6Gas *(Gauge Pressure at 20℃)* | MPa | 0.03 |
| 13 | Minimum Functional Pressure of SF6Gas *(Gauge Pressure at 20℃)* | MPa | 0.01 |
| 14 | Annual Leakage Rate of SF6Gas | - | ≤ 0.01% |
| 15 | Internal Arc Classification | - | IAC A(FLR) 31.5kA /0.5s |
| 16 | Applicable Altitude | m | ≤ 5000 |